Uploader: Jesse
Country: Belgium
Uploaded: Jun 18, 2018
Price: Free

Please, verify you are not robot to load rest of pages

download hvac duct construction standards metal and flexible 3rd edition pdf

ANSI/SMACNA 006-2006
HVAC Duct Construction Standards
Eli P. Howard, III
Sheet Metal and Air Conditioning
Contractors’ National Association
Documents Preceding 3rd Edition
HVAC-DCS
HVAC Duct Construction Standards -Metal and Flexible
– First Edition 1985
– Second Edition 1995
Model Codes
ICC
International Mechanical Code (IMC)
IAPMO
Uniform Mechanical Code (UMC)
NFPA
90A & 90B
HVAC-DCS 3rd Edition 2005
Physical Duct Specimen Testing
Finite Element Analysis (FEA) Modeling
ANSI/SMACNA HVAC-DCS Chapter 11
“Functional Criteria For Ducts”
Finite Element Analysis (FEA)
Translational / Rotational Restraint
Internal / External Pressure (+/-)
Total Displacement
Surface & Membrane Stress (Panel,
Joints, Seams)
HVAC Duct Construction
Standards
WHAT? WHY?
HOW?
1. Review Joints and Limitations
2. Reinforcements – Joints and External
Structural Members
3. Use of the Pressure Class Tables
4. Mid-Panel Tie Rods (MPTs)
Chapter 1
Model Specs
Duct Sealing
Dependent Variables
Information Required for Duct
Construction
1. A comprehensive duct layout indicating
sizes, design airflows, pressure class,
and routing of the duct system.
2. The types of fittings to be used based on
the designer's calculations of fitting
losses (i.e., square versus 45° entry taps,
conical versus straight taps, etc.).
Information Required for Duct
Construction
3. Use of turning vanes or splitter vanes.
4. Location of access doors.
5. Location and type of control and
balancing dampers.
6. Location and types of diffusers.
7. Requirements for duct insulation.
Information Required for Duct
Construction
8. Location and types of any fire
protection device including fire
dampers, smoke dampers, combination
fire/smoke dampers, and ceiling
dampers. Building codes require this
information to be shown on the design
documents submitted for building
permit.
ENGINEER
Design Considerations:
CONTRACTOR
Construction Considerations:
CFM
Panel Thickness (Gage)
Static Pressure
Pressure Class (as specified)
Duct Size
Panel Width/Height
Fitting Type
Joint Type/Spacing
Construction Pressure
Class
Intermediate Reinforcement
Type/Spacing
DEPENDENT VARIABLES
REGULAR DUCTS
Maximum Deflection
Maximum Test
Pressure
Joint and Reinf.
Duct Wall:
Lab:
1/4" on 48" w.
3/8" on 12" Dn.
Class Rating + 50%
W/200 on
1/2" on 13"-18"
49"-120"
5/8"on 19"-24"
Field: